Electrical specifications
DC spark-over voltage 1) 2) |
600 |
V |
|
Tolerance |
±20 |
% |
|
Min. |
480 |
V |
|
Max. |
720 |
V |
|
Impulse spark-over voltage |
|
|
|
at 100 V/µs - for 99% of measured values |
< 850 |
V |
|
- typical values of distribution |
< 750 |
V |
|
at 1 kV/µs - for 99% of measured values |
< 950 |
V |
|
- typical values of distribution |
< 850 |
V |
|
Service life 10 operations 50 Hz, 1 s 1 operation 50 Hz, 0.18 s (9 cycles) 10 operations 8/20 µs 1 operation 8/20 µs 1 operation 10/350 µs |
5 |
A |
|
65 |
A |
||
5 |
kA |
||
10 |
kA |
||
1 |
kA |
||
Max. follow current during one voltage half cycle at 50 Hz |
200 |
A |
|
Insulation resistance at 100 VDC |
> 10 |
GΩ |
|
Capacitance at 1 MHz |
< 1.5 |
pF |
|
Arc voltage at 1 A |
~ 28 |
V A V |
|
Glow to arc transition current |
< 0.3 |
||
Glow voltage |
~ 180 |
||
Weight |
~ 1.5 |
g |
|
Operation and storage temperature |
-40 ... +125 |
°C |
|
Climatic category (IEC 60068-1) |
40/125/21 |
||
Marking, red positive |
EF 600 YY O |
EF 600 YY O - Series - Nominal voltage - Year of production - Non radioactive |
|
Certification |
UL 1449 (E319264) |
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12 and IEC 61643-311.