TDK EPCOS GDT Gas Discharge Tube B88069X0720S102 EC90X
Electrical specifications
DC spark-over voltage 1) 2) |
90 |
V |
||
Tolerance |
±20 |
% |
||
Min. |
72 |
V |
||
Max. |
108 |
V |
||
Impulse spark-over voltage |
|
|
||
at 100 V/µs |
- for 99% of measured values |
< 500 |
V |
|
|
- typical values of distribution |
< 450 |
V |
|
at 1 kV/µs |
- for 99% of measured values |
< 600 |
V |
|
|
- typical values of distribution |
< 550 |
V |
|
Service life |
|
|
|
|
10 operations |
50 Hz, 1 s |
5 |
A |
|
1 operation |
50 Hz, 0.18 s (9 cycles) |
20 |
A |
|
10 operations |
8/20 µs |
5 |
kA |
|
1 operation |
8/20 µs |
10 |
kA |
|
1 operation |
10/350 µs |
1 |
kA |
|
300 operations |
10/1000 µs |
100 |
A |
|
Insulation resistance at 100 VDC |
> 1 |
GΩ |
||
Capacitance at 1 MHz |
< 1.5 |
pF |
||
Arc voltage at 1 A |
~ 12 |
V |
||
Glow to arc transition current |
< 0.8 |
A |
||
Glow voltage |
~ 55 |
V |
||
Weight |
~ 1.5 |
g |
||
Operation and storage temperature |
-40 ... +90 |
°C |
||
Climatic category (IEC 60068-1) |
40/ 90/ 21 |
|||
Marking, red positive |
EC 90 YY O |
|
||
EC |
- Series |
|||
90 |
- Nominal voltage |
|||
YY |
- Year of production |
|||
O |
- Non radioactive |
|||
Certification |
UL 497B (E163070) |
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
Terms in accordance with ITU-T Rec. K.12; IEC 61663-2 and IEC 61643-311.
The Others
Our price of GDT is particularly good. Because we have been serving many customers in the lightning protection industry for decades.
So we also have high quality lightning protection products.
-
Applications:
● Branch exchange● Line protection● Subscriber protection● Alarm system● Tuner● Antenna protection